be forwarded to the Eugene Springfield Fire Marshal's Office in order to update fire department <br />records. <br />Exception: Group R, SR and U occupancies. <br />38. Section 604.3.2 of the OFC is amended to provide: <br />604.3.2 Written Record. Written records of the inspection, testing and maintenance of <br />emergency and standby power systems shall include the date of service, name of the servicing <br />technician, a summary of conditions noted and-a detailed description of any conditions requiring <br />correction and what corrective action was taken. Such records shall be kept on the premises <br />served by the emergency or standby power system and be available for inspection by the fire <br />code official. Within 30 days of performing the annual maintenance inspection and testing a <br />report shall be forwarded to the Eugene Springfield Fire Department Fire Marshal's Office: <br />39. Section 901.5 of the OFC is amended to provide: <br />901.5 Installation Acceptance Testing. Fire detection and alarm systems, fire- <br />extinguishing systems, private fire hydrant systems, fire standpipe systems, fire pump systems, <br />private fire service mains, -smoke and heat ventilators, smoke-removal systems, hazardous <br />materials protection and detection systems, and all other fire protection systems and <br />appurtenances thereto shall be subject to acceptance tests as contained in the installation <br />standards and as approved by the fire code official. The fire code official. shall be notified before <br />any required acceptance testing. <br />40. Section 901.5 of the OFC is amended by adding subsection 901.5.2 to provide: <br />901.5.2 System Plans and Specifications. Fire detection and alarm systems; fire <br />extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private <br />fire service mains and all other fire protection system plans and specifications shall be readily <br />available on the premises. Notation of the precise location of the plans and specifications shall be <br />affixed to the device control panel or major component. Plans and specifications shall consist of <br />the complete construction submittal that was approved by the code official of the jurisdiction of <br />the installation except that any drawings will be as-built drawings delineating actual installation <br />details that are present at system acceptance. <br />41. Section 901.6 of the OFC is amended to provide: <br />Section 901.6 Inspection, testing and maintenance. Fire detection, alarin and <br />extinguishing systems shall be maintained in an operative condition at all time, and shall be <br />replaced or repaired where defective. Nonrequired fire protection systems and equipment shall <br />be inspected, tested and maintained or removed. -The burden of proof concerning whether an <br />installed system is required shall be borne by the'responsible person. All inspections, testing and <br />maintenance shall be completed by a qualified person or company. <br />0 Administrative Order - Page 10 of 14 <br />70 <br />